48 Reference & Installation Manual
3.6.13 Beep Timer For Door Left Open Alarm
SECTION [012]
Enter any value between 001 and 255 to determine the number of seconds
the Access Alarm will beep. Default = 5 seconds.
3.6.14 Door Forced Open Access Alarm
SECTION [006]: OPTION [3]
When the Door Forced Open Alarm is disabled, the following sections are
also disabled:
Option [3] OFF=Door Forced Open Alarm is disabled
(default)
Option [3] ON=Door Forced Open Alarm is enabled
3.6.15 Door Forced Open Feedback
SECTION [004]: OPTIONS [7] AND [8]
Option [7] OFF=Door Forced Open Alarm is silent
Option [7] ON=Door Forced Open Alarm is audible (default)
If option [7] is enabled:
Option [8] OFF=Will beep as long as Door Forced Open Alarm is occurring
(default)
Option [8] ON=Door Forced Open Alarm follows Beep Timer. (section
[013])
3.6.16 Beep Timer For Door Forced Open Alarm
SECTION [013]
Enter any value between 001 and 255 to determine the number of seconds
the Door Forced Open Alarm will beep. Default = 5 seconds.
3.6.17 PIN Entry ON Keypad
SECTION [006]: OPTION [4]
If the Card and Code Access option is enabled in the EVO control panel,
users must present their access control card and then enter their PIN on
the EVO641R keypad to gain access. The PIN Entry on Keypad option
cannot be turned ON and will always be OFF.
4.1 DGP2-648BL Programming
4.1.1 Partition Display
Section [001] to [008]
You can program the LED keypad to display up to four partitions. Sections
[001] to [008] correspond to partitions 1 to 8. The LED numbers A1 to A4
are assigned values 001 to 004 (Figure 29). To assign a display number to
a partition, choose a section number from [001] to [008] and assign it a
value between 001 and 004 which represents LED numbers A1 to A4
respectively
Figure 28: .: Keypad Overview
Figure 29: : LED Partition Display
Do not assign the same display number to more than one section.
For example, you cannot assign value 002 to sections [003] and
[004]. The rejection beep will remind you that a selected display
number is already assigned to another section.
4.1.2 Zone Display
Section [101] To [196]
You can program the keypad to display up to a total of 48. Sections [101] to
[196] correspond to zones 1 to 96 respectively. These zones are displayed
on LED numbers 1 to 48 and are assigned values 001 to 048.
Do not assign more than one LED number to a zone. For example,
you cannot assign LED number 33 to zones 21 and 28. The
rejection beep will remind you that a selected LED number is
already assigned to another section.
Every time the [
CLEAR] key is pressed it will revert to the preceding
step, unless entering in data in which case it will erase the current
entry.
4.1.3 Section Reset
Section [040]
This section resets zone display sections [101] to [196] to default settings.
Enter [040] to perform the reset.
4.1.4 Confidential Mode
Section [009] Option [1]
In Confidential Mode all LEDs will turn off until either a button is pressed or
an access code is entered.
Option [1] OFF = Disabled (default).
Option [1] ON = Enabled.
Table 18: Door Forced Open Access Alarm
Section
[004] Option [7] Door Forced Open Alarm
Option [8] Door Forced Open Alarm
follows
[013] Beep Timer for Door Forced Open Alarm
[ENTER] Saves current data and exits current menu.
[
CLEAR] Erases current data entry or reverts to the preceding step.
Partition Lights: (A1, A2, A3 and A4)
ON = Partition armed
OFF = Partition disarmed
FLASH = Partition in alarm
Action Lights: (Access, Stay,
Force, Mem, Trbl and Prg)
Lights will illuminate according
to the status of the system.
Numerical Lights: (Zones)
ON = Open / breached
OFF = OK
FLASHES = Tamper / fire loop
“AC” Light:
ON = AC Power
OFF = Power failure
“Status” Light:
When green:
ON = All zones closed
OFF = Zone(s) open
FLASH = Exit Delay in progress
When red:
ON = All partitions armed
OFF = Partition disarmed
FLASH = Partition in alarm
Keypad will display the status
of all its assigned partitions.
Value: 001 002 003 004