Enabling the ATZ feature allows you to install two detection devices per zone input terminal. Each detection device
will have its own zone, displaying zone status on the keypad and sending separate alarm codes for each zone. The
extra zones are recognized as described in Table 4 on page 16 or i n Figure 5-4 below. For more i nformation on how
to connect to detection devices, please refer to Double Zone Inputs on page 8.
When a zone is defined as a Keyswitch or a Fire Zone and the ATZ feature is enabled, the control
panel will disable the “doubled zone” .
Figure 5.4: Zone Recognition with ATZ enabled
PART 6: ARMING AND DISARMING OPTIONS
6.1 SWITCH TO STAY AR MING
Section [133] = Partition 1, Section [134] = Partition 2
Option [4] OFF = Switch to Stay Arming Disabled (default)
Option [4] ON = Switch to Stay Arming Enabled
If a user Regular arms a partition, but does not exit through (open and close) an Entry Delay zone during the Exit
Delay, the control panel can be programmed to switch from Regular Arming to Stay Arming.
6.2 STAY ARMING WITH DELAY
Section [133] = Partition 1, Section [134] = Partition 2
Option [5] OFF = Stay Arming with Delay Disabled (default)
Option [5] ON = Stay Arming with Delay Enabled
When a partition is Stay Armed when this featur e is enabled, all the zones in the par tition, except 24Hr. zones, are
associated with the Stay Delay. Therefore, the control panel will not generate an alarm if a zone is breached until the
Stay Delay has elapsed. This feature prevents false alarms by allowing users enough time to disarm their system if
a zone is accidentally triggered. For example, if a user opens an armed window or crosses an armed detector on the
way to the kitchen in the middle of the night, the user will have enough time to disarm the system before the alarm is
generated. Each partition’s Stay Delay follows the value programmed in Entry Delay Timer 2 in section [070].