The keypads must be assigned to the same partition as the
Delayed 24Hr Fire zone for the buzzer to activate.
Figure 5-3: Delayed 24Hr Fire Zone
5.3.13 Standard 24Hr Fire Zone
A zone programmed as Fire becomes normally open (will not function as
normally closed) and requires an EOL resistor.
When a Standard 24Hr Fire Zone triggers, the control panel can:
• send a Zone Alarm report code (see section 9.2.1 on page 28).
• send a Fire Loop Trouble Report (see section 9.2.11 on page 29) if a
tamper/wiring fault occurs on a Fire Zone. A “Zone Fault Trouble” will
also appear in the keypad's Trouble Display.
• generate a Fire alarm, which is always audible, regardless of other
settings. Fire alarms generate an intermittent signal (see Figure 5-4).
Figure 5-4: Bell/Siren Output During Fire Alarm
5.3.14 Stay Delay Zone
When a Stay Delay zone is armed using the Regular or Force arming
methods, the control panel processes the zone as an Instant zone (see
section 5.3.4). When a Stay Delay zone is armed using the Stay or Instant
arming methods and the zone is triggered, the control panel will not
generate an alarm until the programmed Stay Delay elapses. A zone
defined as Stay Delay 1 follows the Entry Delay 1 Timer of its assigned
partition. Likewise, a zone defined as Stay Delay 2 follows the Entry Delay
2 Timer of its assigned partition. To program the Entry Delay Timers, refer
to Entry Delays 1 and 2 on pag e17.
For example, if zone 1 in Partition 5 is defined as Stay Delay 1, the timer
will follow the amount programmed in [3511].
5.4 Z
ONE
P
ARTITION
A
SSIGNMENT
A control panel can be divided into eight completely independent systems
(see section 12.7 on page 35). Assign each zone to one partition (see
Figure 5-1 on page 16).
5.5 Z
ONE
O
PTIONS
The zone options from Figure 5-1 on page 16 are described below.
5.5.1 Auto Zone Shutdown
(Default = 000) When option [1] is disabled, the control panel generates an
alarm when an armed zone is breached even if the same zone opens
repeatedly during the same alarm, which may cause several reportings and
further activation of the bell output. When option [1] is enabled, the control
panel will stop regenerating alarms on the zone during the same armed
period once the Auto Zone Shutdown Limit is reached. The Auto Zone
Shutdown Limit resets every time the system is armed. To program the
Auto Zone Shutdown Limit, key in the desired 3-digit counter (000 to 255)
into section corresponding to the desired partition (000 = disabled):
5.5.2 Bypass Zones
Only zones with option [2] enabled can be Manually Bypassed (see section
16.6). Fire Zones cannot be bypassed. Default = enabled.
5.5.3 Stay Zones
Only zones with option [3] enabled will be bypassed when the partition is
Stay Armed (see section 16.2) or Instant Armed (see section 16.3). All
other zones will remain activated. Fire Zones cannot be set as Stay Zones.
5.5.4 Force Zones
Only zones with option [4] enabled can be bypassed when the partition is
Force armed (see section 16.4). Fire Zones cannot be Force Zones.
Delayed Fire Zone
Triggered
Activate bell/siren output & delay
report transmission for 30 seconds.
Yes
Yes
Any key on
keypad pressed
within 30
seconds?
Bell/siren silenced. Delay report
transmission an additional 90 sec.
Problem
corrected?
Latch alarm and transmit
report code as described
in the section "Standard
24Hr. Fire Zone".
END
Alarm Disabled
No
Has a 2nd
Delayed Fire
Zone opened in
30 sec.?
No
Yes
Yes
No
Has the zone
closed within
30 seconds?
Yes
No
Partition 1: [3114] Partition 5: [3514]
Partition 2: [3214] Partition 6: [3614]
Partition 3: [3314] Partition 7: [3714]
Partition 4: [3414] Partition 8: [3814]