22 REFERENCE & INSTALLATION MANUAL
7.5.1 Tamper Bypass Options
SECTION [3034]: OPTION [7]
(Default = enabled) With option [7] enabled in section [3034], the control
panel will ignore the zone’s bypass definition and will follow the option set in
section 7.5 if a tamper or wire fault occurs on a bypassed zone. With option
[7] disabled, Tamper Recognition follows the zone’s bypass definition. This
means that the control panel will not perform any action if a tamper or wire
fault occurs on a bypassed zone.
7.6 KEYPAD PANIC OPTIONS
(Default = disabled) The control panel can generate an alarm (audible, fire
or report only) by pressing the keypad Panic key(s). For LCD keypads, two
keys are pressed and held simultaneously for 2 seconds. For Grafica
keypads, the appropriate Panic key is pressed and held for 2 seconds.
Refer to the table below for the keypad Panic keys. In the section that
corresponds to the desired partition, enable or disable options [1] through
[6] as desired:
REPORT ONLY
The keypad emits a single Confirmation Beep and transmits the appropriate
report code (see section 8.2.10).
AUDIBLE ALARM
The control panel activates the BELL output until a user cancels the alarm
with a valid User Access Code or when the Bell Cut-Off Timer elapses (see
section 7.2).
FIRE ALARM
Same as audible operation, except that the bell/siren output will be pulsed
as shown in Figure 4-4 on page 14.
* UL Note: For UL Listed systems, all emergency non-medical and auxiliary
panic alarms shall be report only.
Partition 1: [3123] Partition 3: [3323] Partition 5: [3523] Partition 7: [3723]
Partition 2: [3223] Partition 4: [3423] Partition 6: [3623] Partition 8: [3823]
Option Feature Press and Hold:
[1] Panic 1*
LCD keypads: Keys [1] and [3] simultaneously
Grafica keypads: The key
[2] Panic 2*
LCD keypads: Keys [4] and [6] simultaneously
Grafica keypads: The key
[3] Panic 3
LCD keypads: Keys [7] and [9] simultaneously
Grafica keypads: The key
Option Alarm Type
[4] Panic 1:*
ON = Audible
OFF = Report Only
[5] Panic 2:*
ON = Audible
OFF = Report Only
[6] Panic 3:
ON = Fire
OFF = Report Only