To make your CO Detector tamper resistant, a locking pin has been provided in the bag
with the screws and anchors. Using this pin will deter children and others from removing
the Detector from the mounting plate. To use the pin insert it into the hole in the side
of the Detector after the Detector has been installed on the mounting plate (figure 14).
To remove the Detector, use long nose pliers pull the pin out of the hole; it is now possible
to remove the Detector from the mounting plate.
The Detector box contains two self-adhesive labels. You should write the telephone
numbers of the emergency service provider and a qualified technician in the space
provided on the labels. Place one label next to the Detector, and the other label near a
source of fresh air where you plan to gather after the Detector indicates the presence of
carbon monoxide.
CO DETECTOR REPLACEMENT PROCEDURE
CAUTION: When a CO Detector is removed from the UltraGuard system for replacement, it will cause a trouble
condition (-- pause -- on the monitor zone lights). You must notify your central monitoring company before replacing
the CO Detectors. The alarm may be silenced by pressing the RESET button (item j, figure 1, page 3). Replacing
the CO Detector will return the UltraGuard to normal operation.
The first (closest to the Monitor) and last (farthest from the Monitor) Detectors for each zone have unique internal configurations
(see figures 11, 11a, 12, 12a, pages 12-13 ).
Please make sure that the internal configuration is replicated:
If the old Detector has resistors and jumper install them into the new Detector
If the old detector does not have resistors and jumpers leave contacts empty.
IF THE ORIGINAL SETUP IS NOT REPLICATED THE DETECTORS WILL NOT WORK!
CAUTION: When the installation is complete it must be verified with the CO Detector test button. When the CO
Detector test button is pressed the UltraGuard yellow trouble light must light at the same time as the red zone light.
if the yellow light is delayed by two or three seconds these resistors are not installed correctly and the system will
not shut the furnace down correctly.
After replacing the CO Detectors it is necessary to reset the internal 5-year clock on UltraGuard Monitor and the indicator lights
(items m, nopqand r, figure 1, page 3). Press and hold the RESET button until the Replace Detectors light goes out and
the UltraGuard Monitor alarm chirps (2 to 5 seconds).